Specifications
Nominal voltage, V | 12 |
Nominal capacity, Ah | 120,24 |
Design life, years | 10-12 |
Technology | AGM |
Length, mm | 406 |
Width, mm | 172 |
Height,mm | 223 |
Height without terminals, mm | 223 |
Height max,mm | 228 |
Weight, kg | 37,4 (±3%) |
Description
The ASTERION DTM I series sealed lead-acid batteries are manufactured using AGM technology (electrolyte absorbed in a fiberglass separator), equipped with an LCD display that shows the battery operation status: voltage, capacity and number of days in use. DTM I series relates to the "Long Life" product line with up to 12 years service life , with the possibility of increasing it by 15-30% with a single replenishment (topping up) of a specialized component solution. They are recommended for use in uninterruptible power supplies, in electro-medical equipment, wheelchairs, boilers for heating systems, pumps, etc.
Battery construction
Element | Positive plate | Negative plate | Case | Lid | Valve | Terminal | Separator | Electrolyte |
---|---|---|---|---|---|---|---|
Material | Lead dioxide | Lead | ABS | Rubber | Copper | Fiberglass | Acid |
Performance & characteristics:
- LCD display showing battery status;
- Sound alarm in case of need to check the battery;
- Compliance with the UL requirements;
- Additional containers for topping up a specialized solution allow to increase battery life up to 15-30%;
- Patented IC Power Technology;
- High energy density;
- The battery case is made of flame-retardant ABS plastic.
Application:
- Uninterruptable power supply
- Back up power supply
- Medical devices
- Control current cabinet
- Space-heating system
- Heating and water supply systems
Operating temperature range
Discharge | -20÷60 |
---|---|
Charge | -10÷60 |
Storage | -20÷60 |
Cycle mode (2,35÷2,4 V/cell): | |
Maximum discharge current | 950 А |
Temperature correction factor | 30 mV/°С |
Standby mode (2,25÷2,3 V/cell): | |
Temperature correction factor | 20 mV/°С |
Discharge Constant Current, A ( 25°С)
V/cell | 5 min | 10 min | 15 min | 30 min | 45 min | 1 h | 3 h | 5 h | 10 h |
---|---|---|---|---|---|---|---|---|---|
1.60V | 355 | 254 | 205 | 115 | 85,4 | 72,1 | 29,4 | 20,0 | 12,2 |
1.65V | 329 | 240 | 198 | 112 | 84,2 | 71,7 | 28,9 | 19,8 | 12,2 |
1.70V | 307 | 228 | 190 | 108 | 81,8 | 70,2 | 28,3 |
19,4 |
12,1 |
1.75V | 289 | 213 | 181 | 104 | 78,9 | 67,9 | 27,5 |
18,9 |
12,0 |
1.80V | 268 | 200 | 174 | 102 | 77,0 | 65,9 | 26,7 |
18,6 |
12,0 |
Discharge Constant Power, W/cell ( 25°С)
V/cell | 5 min | 10 min | 15 min | 30 min | 45 min | 1 h | 3 h | 5 h | 10 h |
---|---|---|---|---|---|---|---|---|---|
1.60V | 811 | 595 | 496 | 311 | 228 | 183 | 77,7 | 52,6 | 29,7 |
1.65V | 769 | 574 | 478 | 306 | 222 | 179 | 75,7 | 51,6 | 29,7 |
1.70V | 734 | 550 | 463 | 302 | 215 | 175 | 73,8 | 50,1 | 29,5 |
1.75V | 696 | 527 | 444 |
292 |
209 |
171 |
72,1 |
49,2 | 29,3 |
1.80V | 674 | 505 | 428 | 282 | 203 | 167 | 70,2 | 47,9 | 29,3 |